Applications
Level indication, alarming and control of various liquids.
Features
Hall ICs improved long-term stability.
When current flows in an X direction on a semiconductor, electrons move in the opposite direction. When an external magnetic field is applied in a Y direction, electrons experience an electromagnetic force.
A left hand can represent these three mutually orthogonal axes: force on the thumb, field on the first finger and current on the second finger. (Fleming's left-hand rule)
The change in the strength of the magnetic field causes change in strength of the electric field, changing the output voltage proportionally. This is called the Hall effect. Hall ICs utilize this effect.
Principle of Operation
The product is comprised of a float and a stem. The float has a magnet inside. The stem incorporates a circuit board with several Hall ICs and resistors placed at regular intervals.
Fig.1 shows operation of the float and the Hall ICs. Fig.2 shows the circuit in the stem.
Fig. 1: Operation of float and Hall ICs Fig. 2: Circuit in the stem
For a rising level, float location and Hall ICs in operation change as shown in Fig.1, from A(2 ICs in operation) to B (3 ICs in operation), then to C (2 ICs in operation). For a falling level, from C to B, then to A.
This means that the combined resistance changes as the float rises or falls. The electronics in the sensor housing measures the combined resistance, converts it to signals, and then amplify and calibrate the signals to give current output (2 wire, 4 to 20mA DC).
Voltage output is also available by connecting a current-to-voltage converter or a precision resistor to the output terminal.
|
Resistive Level Measurement LR420 (Hall ICs)|PROCESS Resistive
Level Measurement LR420 (Hall ICs). Applications. Level indication,
alarming and control of various liquids. Features. Resistive Level
Measurement LR420 (Hall ICs). Insensitive to process conditions such
as pressure, temperature and specific gravity. Integrated protection circuit
protects connected devices in the ... Resistive level measurement
LR|PROCESS AUTOMATION NOHKEN Resistive level measurement LR.
Applications. Pressure vessels or chemical tanks such as hydraulic acid or
sulfuric acid. Features. Resistive level measurement LR.
Insensitive to process conditions such as pressure, temperature and specific
gravity. Various wetted parts material to choose from for specific
application ... Resistive liquid level/temperature sensor and transmitter A resistive liquid level/temperature
sensor and transmitter including low voltage impedancemeasurement circuitry
to convert three impedance values into indications of the temperature and the
levels of two different liquids (e.g., oil and water) located within a storage
tank. A resistive chain network including a plurality
of ...
Level Measurement - OMEGA Engineering Like ultrasonic
sensors, capacitance sensors can handle point or continuous level
measurement. They use a probe to monitor liquid level changes in the tank,
electronically conditioning the output to capacitive and resistive values,
which are converted to analog signals. The probe and the vessel wall equate to
two plates of ... Level measurement 9AEI306.77 28 Principle of Resistive type Level Indicator
• The float acts as a primary transducer that converts liquid level variation
into a suitable displacement • This displacement is sensed by the secondary
transducer such as a resistive potentiometric device • The resistivepotentiometer
converts ... Level sensor – Wikipedia Loncat ke Resistive chain - These
sensors work well for liquid level measurements in marine,
chemical processing, pharmaceuticals, food processing, waste treatment, and
other applications. With the proper choice of two floats, resistive chain
level sensors can also be used to monitor for the presence of an
interface ...
Resistive level sensor HARDWARE FEATURES. Device Functionality.
OTC Wireless Transmitter that Supports Resistive Level Sensors.
LL3: 1/2" Resolution; 3-in-1 Monitoring: Product, Interface and
Temperature (6-pin Quick Connect). LL3-D: 1/2" Resolution, 4-in-1:
Discrete Input + Product, Interface and Temperature (6-pin Quick Connect). Resistive
Inductive and capacitive methods for level measurement Resistive, Inductive and capacitive
methods for level measurement D.Patranobis, Principles of
Industrial Instrumentation Day 29 Measurement of level using Gamma rays
D.Patranobis, Principles of Industrial Instrumentation Day 30 Ultasonic methods
D.Patranobis, Principles of Industrial Instrumentation Day 31 ... Explosion
Proof Resistive Level Transmitter with 1" Stem This float level transmitter is
the ultimate in durability. It's commonly referred to in the field as a mud
probe, one of the most demanding applications around. It's also well suited for
extreme sewage level measurement and has PDA approval for
marine applications.